FDU 520Q0T2/101-0K1
Part #KS84368003
Operation Type : Continuous (520)
Main Voltage : 120 V AC, 50/60 Hz (Q)
Flame Control : Flame rod (0)
Electrical Connection Type : Screw terminals (K1)
The FDU series provides OEMs, burner manufacturers, and end users with a state-of-the-art flame monitoring capability for gas burners across a wide range of applications – from hot-air furnaces and gas-fired boilers to industrial furnaces and excess-gas flaring installations.
Replacing the IFW 15/50, Honeywell's R4343, and BC1000 flame relay models, the new FDU enables multi-flame control or multi-point monitoring in conjunction with burner control units (BCUs) such as the BCU 560 or a failsafe PLC with a standard-compliant flame monitoring device.
The FDU 520 monitors gas burners in continuous/permanent operation (applications of more than 24 hours). The compact footprint of these units means that they can be easily integrated and mounted with other equipment in a cabinet, providing convenient access for maintenance and repair. The FDU can be installed on a DIN rail in the control cabinet. Plug-in connection terminal strips on the FDU make it easier to install and remove.
The flame detectors are also suitable for multi-point burner monitoring and multi-flame control when used with a Kromschröder BCU 5 series
Using the BCSoft program and the optional opto-adapter PCO 200, it is possible to set parameters to suit an application and also to read analysis and diagnostic information from the flame detector.
-
Certifications
- FM
- UL
- cUL recognized
- CE
Ratings
- Ambient temperature: -4°F to 140°F (-20°C to 60°C)
- Enclosure: IP 20
-
FDU Flame detector Series 510 For intermittent operation 520 For continuous operation Main voltage W 230 V AC, 50/60 Hz Q 120 V AC, 50/60 Hz Flame control 0 Flame control with flame rod 1 Flame control with UVS 2 Flame control with UVC 9 Flame control with series C7027, C7035, C7044 Switch-off threshold T2 2 micro A T5 5 micro A T7 7 micro A Reaction time in the event of flame failure /1 1 s /4 4 s Flame report O1 1 NO contact, 1 NC contact O2 2 NO contacts Flame signal intensity -0 No output -1 0-5 V output Connection plugs K1 With screw terminals K2 With spring force terminals