BCU 370QFEU0D1
Part #KS88600861
BCU Type : 370
Main Voltage : 120 V AC, 50/60 Hz (Q)
Digital Input Function : DGmax monitoring (D1)
The BCU 370 burner control unit ignites and monitors industrial forced draught burners of unlimited capacity in intermittent or continuous operation.
It can be used for directly ignited forced draught burners or forced draught burners ignited by a pilot burner. The BCU 370 activates the fan and sets the connected butterfly valve to pre-purge and ignition positions. After pre-purge and burner start, the controller enable signal is issued to an external controller which positions the butterfly valve in accordance with the capacity demand. Post-purge occurs after the end of burner operation. The burner control unit BCU 370 monitors the gas and air pressure. An optionally integrated tightness control function checks the valves with an external gas pressure switch.
The quick-start option allows standard-compliant start-up of the forced draught burner without pre-purge after a controlled shut-down. This avoids unnecessary admission of air into the combustion chamber. The heat output is available as quickly as possible after a temperature demand.
The program status, the device parameters, and the level of the flame signal can be read directly from the BCU. An integrated Manual mode allows manual start of the burner and setting of the butterfly valve position independently of the central control system. The BCSoft operator-control and setting software provides a powerful tool for commissioning and servicing.
To reduce the installation and wiring costs, KromAmericas offers an optional PROFIBUS DP interface to transfer the activation signals and feedbacks.
-
- For modulating, forced draught burners for gas of unlimited capacity in intermittent or continuous operation
- Control of fan and butterfly valve
- Simple system set-up thanks to optional tightness control and integrated ignition unit
- Easy start-up and maintenance thanks to Manual operating mode
-
Certifications
- FM
- CSA
- UL
- cUL
- UKCA
- CE
- EAC
Ratings
- Ambient temperature: -4°F to 140°F (-20°C to 60°C)
- Enclosure: IP 54
-
BCU 370 Burner control unit Main voltage Q 120 V AC, 50/60 Hz W 230 V AC, 50/60 Hz Electronic ignition I1 Single-pole I2 Double-pole I3 Double-pole with neutral conductor Fan control F 3 A relay Valve control E Three-point step Flame control U0 Ionization control (continuous or intermittent operation) or UV control (intermittent operation with UVS) U1 UV control (continuous operation with UVD) Digital input function D1 DGmax. monitoring D3 Integrated tightness control Fieldbus interface B1 PROFIBUS DP Bus control -3 Three-point step